Add ERV mapping to baseline workflow - #35

Open
JieXiong9119 wants to merge 14 commits into
developfrom
add-erv-mapping-to-baseline
Open

JieXiong9119 wants to merge 14 commits into
developfrom
add-erv-mapping-to-baseline

Conversation

@JieXiong9119

Copy link
Copy Markdown
Contributor

Summary

Maps BuildingSync energy recovery ventilators (ERVs) onto L200 topology baselines using ComStock heat recovery. When a recovery record's VentilationType is Energy recovery ventilator, the baseline workflow overrides heat exchanger effectiveness with ComStock's ERV values.

Depends on buildingsync-measures-gem add-comstock-erv-preset, which adds the comstock_erv option to modify_existing_heat_recovery.

Changes

  • HvacTopologySelector: the recovery match now passes the record's VentilationType in measure_arguments as ventilation_type.
  • BaselineHvacPlanner:
    • When any recovery result is an ERV, adds a modify_existing_heat_recovery step (target_heat_exchanger_names: '*', effectiveness_metric: 'comstock_erv') right after the ComStock recovery step.
    • Mixed HRV and ERV records fall back to the template baseline, because ComStock recovery applies to the whole model. The fallback reason is: "Mixed heat and energy recovery ventilators are not supported; ComStock recovery is model-wide."
  • Recovery mapping cleanup (earlier on this branch):
    • Removed the validator measure.
    • An economizer-only delivery is now folded into its central delivery.
    • Recovery Integration is inferred when every linked delivery is central air.
  • README: documents the ERV override and the mixed HRV/ERV fallback.

Testing

  • Unit specs: 172 examples, 0 failures. New tests cover the ERV step, the mixed-type fallback, measure_arguments, and the step order for the Example_ASHRAE_L2_Report_l200_erv.xml fixture.
  • Integration, write and run an L200 baseline with ComStock recovery (Example_ASHRAE_L2_Report_l200_erv.xml):
    • The workflow and every step succeeded.
    • heat_exchangers_updated matched the number of created loops.
    • The final model (baseline/in.osm) has 45 exchangers with ComStock ERV values: sensible 0.675 and latent 0.549 at 100% heating flow.
    • The full spec has not been rerun since its model path was corrected. The corrected assertion was checked directly against the saved model.
  • Integration regression: 5 examples, 0 failures.
    • Both small-office topology baselines.
    • Example_ASHRAE_L2_Report.xml.
    • BuildingEQ-1.0.0.xml.
    • all_measures_applied_example.xml.
  • git diff --check is clean. RuboCop was not run.

Notes / follow-ups

  • The override applies to every heat exchanger in the model, so per-system HRV/ERV mixes are not supported yet.